Begin with the PCS DC window
Select nominal and operating voltage from the actual PCS or inverter range, not from a preferred cabinet size.
240V · 384V · 480/512V cabinet systems
Catalogue-defined high-voltage battery cabinets from 24kWh to 153.6kWh for ESS projects that require coordinated BMS, PCS, protection, communication and commissioning.


Installation planning
Cabinet voltage, PCS operating range, isolation, emergency shutdown, cable routing and commissioning responsibilities must be designed as one system. Include the equipment model and installation drawing with your inquiry.
Product range
The catalogue separates a 240V/384V cabinet group from a 480V platform with an adjustable rated voltage listed at 512V. Energy spans 24–76.8kWh in the 240V/384V group and 48/51.2–144/153.6kWh in single-cluster 480V models. These are system components, not standalone appliances: the PCS or inverter, HV protection, controls, emergency shutdown, installation and acceptance test boundary must be defined together.
Model comparison
These figures come from the manufacturer catalogue. Ask for the current datasheet before final approval or purchase.
| Model | Voltage | Capacity | Energy | Charge voltage | Standard / max. charge | Max. discharge | Size (mm) |
|---|---|---|---|---|---|---|---|
| CLFP240-100-H | 240V | 100Ah | 24kWh | 270V | 50A / 100A | 100A | 600 × 600 × 1400 |
| CLFP240-200-H | 240V | 200Ah | 48kWh | 270V | 100A / 200A | 200A | 600 × 900 × 1400 |
| CLFP384-100-H | 384V | 100Ah | 38.4kWh | 432V | 50A / 100A | 100A | 600 × 600 × 2000 |
| CLFP384-200-H | 384V | 200Ah | 76.8kWh | 432V | 100A / 200A | 200A | 600 × 900 × 2000 |
| CLFP480-100-H | 480V / adjustable 512V | 100Ah | 48 / 51.2kWh | 540V / adjustable 576V | 50A / 100A | 100A | 600 × 600 × 2200 |
| CLFP480-200-H | 480V / adjustable 512V | 200Ah | 96 / 102.4kWh | 540V / adjustable 576V | 100A / 200A | 200A | 600 × 1000 × 2200 |
| CLFP480-300-H | 480V / adjustable 512V | 300Ah | 144 / 153.6kWh | 540V / adjustable 576V | 150A / 300A | 300A | 600 × 1000 × 2000 × 2 |
How to choose
Send the information you already have. We can narrow the model list and point out what still needs to be checked.
Select nominal and operating voltage from the actual PCS or inverter range, not from a preferred cabinet size.
Ah and kWh define stored energy; charge and discharge current define power and cable or protection requirements.
HV isolation, disconnects, pre-charge, emergency shutdown, grounding, fire strategy and commissioning need named responsibility.
Typical applications
Tell us about the equipment and duty cycle. We will help check whether this series is a practical fit.
Peak management, renewable integration or resilience projects with a defined load profile and PCS.
Coordinate batteries with PV, generators, grid connection, EMS and operating modes.
Define critical loads, transfer sequence, runtime, redundancy and restart behaviour.
What you can ask for
Commercial terms vary by model, quantity and destination. Include these questions in your inquiry and we will reply with the current available information.
For an accurate quote
LiFePO4 product range
Product FAQ
We will confirm current availability, documents and commercial terms for the exact model you select.
Choose from the PCS DC operating range, target power, system architecture and protection design. Nominal voltage alone is not enough.
CLFP480-300-H is listed at 300Ah and 144/153.6kWh, using two 600 × 1000 × 2000mm cabinet sections.
The catalogue lists 3,500 cycles at 25°C, 1C/1C and 80% DOD for 240/384V, and 3,000 cycles at the same stated basis for the 480V family.
The 240/384V family lists RS232, RS485 and CAN; the 480V family lists RS485 and CAN.
No. It is a catalogue comparison. Final design requires current model documents, PCS compatibility, protection design, site review and commissioning scope.
Product inquiry
Send the application, voltage, load, runtime, installation space, quantity and destination you know. We will help turn it into a quote-ready request.