Choose sealed or flooded deliberately
NPFG reduces routine electrolyte access; OPzS requires ventilation, electrolyte and maintenance planning.
Stationary GEL and flooded tubular routes
Two long-duration stationary choices that must not be treated as the same product: sealed front-terminal GEL NPFG blocks and serviceable flooded OPzS tubular cells.

Product range
The supplied catalogue page does not show a separate OPzV model table; it shows NPFG front-terminal GEL 12V models from 55Ah to 155Ah and OPzS flooded tubular 2V cells from 150Ah to 1000Ah. OPzS is listed with a 15-year floating design-life statement and more than 1,000 deep cycles. Because OPzS is flooded, electrolyte, ventilation and maintenance planning differ materially from sealed GEL products.
Model comparison
These figures come from the manufacturer catalogue. Ask for the current datasheet before final approval or purchase.
| Family / model | Rating | Size L×W×H (mm) | Dry / filled weight | 1-hour capacity | 10-hour capacity | Construction |
|---|---|---|---|---|---|---|
| NPFG / NP55-12-FG | 12V 55Ah | 277 × 106 × 223 | 18kg | — | 51Ah | Sealed front-terminal GEL |
| NPFG / NP155-12-FG | 12V 155Ah | 551 × 109 × 288 | 50kg | — | 145Ah | Sealed front-terminal GEL |
| OPzS-150 | 2V 150Ah | 103 × 206 × 355 | 10.5 / 15kg | 57Ah | 150Ah | Flooded tubular |
| OPzS-300 | 2V 300Ah | 145 × 206 × 355 | 19.2 / 24.3kg | 115Ah | 300Ah | Flooded tubular |
| OPzS-600 | 2V 600Ah | 145 × 206 × 646 | 33.9 / 44.8kg | 213Ah | 600Ah | Flooded tubular |
| OPzS-1000 | 2V 1000Ah | 233 × 210 × 646 | 55.5 / 74.6kg | 355Ah | 1000Ah | Flooded tubular |
How to choose
Send the information you already have. We can narrow the model list and point out what still needs to be checked.
NPFG reduces routine electrolyte access; OPzS requires ventilation, electrolyte and maintenance planning.
Define DC voltage, cell count, autonomy, end voltage, redundancy and rack footprint.
Check floor loading, spill control, ventilation, inter-cell links, access and lifting before quotation.
Typical applications
Tell us about the equipment and duty cycle. We will help check whether this series is a practical fit.
Long-duration stationary DC systems with defined inspection and maintenance practice.
Projects with repeated cycling, autonomy and a battery room designed for the chosen construction.
NPFG may fit front-access cabinets; OPzS may fit larger maintained stationary rooms.
What you can ask for
Commercial terms vary by model, quantity and destination. Include these questions in your inquiry and we will reply with the current available information.
For an accurate quote
Product FAQ
We will confirm current availability, documents and commercial terms for the exact model you select.
No separate OPzV table is identifiable in the supplied pages. The published comparison therefore uses NPFG sealed GEL and OPzS flooded tubular models and requires a separate current OPzV document for an OPzV quotation.
NPFG is sealed front-terminal GEL in 12V blocks; OPzS is a flooded tubular 2V cell requiring a maintained installation.
The catalogue lists 2V models from 150Ah through 1000Ah.
The catalogue states 15 years design life in floating condition and more than 1,000 deep cycles.
Flooded OPzS cells add electrolyte weight at installation, which affects handling, rack and floor loading.
Product inquiry
Send the application, voltage, load, runtime, installation space, quantity and destination you know. We will help turn it into a quote-ready request.