Stationary GEL and flooded tubular routes

OPzV / OPzS Tubular Battery

Two long-duration stationary choices that must not be treated as the same product: sealed front-terminal GEL NPFG blocks and serviceable flooded OPzS tubular cells.

MANUFACTURED BYGuangdong Zhicheng Champion Group Co., Ltd.Product selection and export inquiry support: Sodium Energy Systems
Champion NPFG front-terminal GEL and OPzS flooded tubular stationary batteries
CHAMPION BATTERY PRODUCT
NPFG12V 55–155Ah
OPzS2V 150–1000Ah
OPzS DESIGN LIFE15 years in float
OPzS CYCLE STATEMENT>1,000 deep cycles

Product range

Models, ratings and practical differences

The supplied catalogue page does not show a separate OPzV model table; it shows NPFG front-terminal GEL 12V models from 55Ah to 155Ah and OPzS flooded tubular 2V cells from 150Ah to 1000Ah. OPzS is listed with a 15-year floating design-life statement and more than 1,000 deep cycles. Because OPzS is flooded, electrolyte, ventilation and maintenance planning differ materially from sealed GEL products.

Model comparison

Compare the ratings that affect your installation.

These figures come from the manufacturer catalogue. Ask for the current datasheet before final approval or purchase.

Family / modelRatingSize L×W×H (mm)Dry / filled weight1-hour capacity10-hour capacityConstruction
NPFG / NP55-12-FG12V 55Ah277 × 106 × 22318kg—51AhSealed front-terminal GEL
NPFG / NP155-12-FG12V 155Ah551 × 109 × 28850kg—145AhSealed front-terminal GEL
OPzS-1502V 150Ah103 × 206 × 35510.5 / 15kg57Ah150AhFlooded tubular
OPzS-3002V 300Ah145 × 206 × 35519.2 / 24.3kg115Ah300AhFlooded tubular
OPzS-6002V 600Ah145 × 206 × 64633.9 / 44.8kg213Ah600AhFlooded tubular
OPzS-10002V 1000Ah233 × 210 × 64655.5 / 74.6kg355Ah1000AhFlooded tubular

How to choose

Start with the load, charger and available space.

Send the information you already have. We can narrow the model list and point out what still needs to be checked.

01

Choose sealed or flooded deliberately

NPFG reduces routine electrolyte access; OPzS requires ventilation, electrolyte and maintenance planning.

02

Size the 2V string

Define DC voltage, cell count, autonomy, end voltage, redundancy and rack footprint.

03

Plan the battery room

Check floor loading, spill control, ventilation, inter-cell links, access and lifting before quotation.

Typical applications

Where buyers use this battery family

Tell us about the equipment and duty cycle. We will help check whether this series is a practical fit.

01

Utility and substation backup

Long-duration stationary DC systems with defined inspection and maintenance practice.

02

Renewable-energy banks

Projects with repeated cycling, autonomy and a battery room designed for the chosen construction.

03

Telecom and infrastructure

NPFG may fit front-access cabinets; OPzS may fit larger maintained stationary rooms.

What you can ask for

Get the information needed for a sourcing decision.

Commercial terms vary by model, quantity and destination. Include these questions in your inquiry and we will reply with the current available information.

01MOQ and sample availability02Current production lead time03Model datasheet and available certificates04Packing, shipment and Incoterm options05Warranty basis and claim process06OEM branding or configuration options

For an accurate quote

Send these details if available

  1. 01Required DC voltage, cell count, autonomy and discharge rate
  2. 02Sealed GEL versus flooded maintenance strategy
  3. 03Room ventilation, floor load, spill control and service access
  4. 04Rack layout, inter-cell connectors, protection and monitoring
  5. 05Current exact-model drawings, capacity data and compliance documents
  6. 06For OPzV inquiries, request a separate current model catalogue because the supplied table does not identify an OPzV series
GEL Lead-Acid Battery→Deep-Cycle Lead-Acid Battery→Request Current OPzV Data→

Product FAQ

Questions buyers ask before ordering

We will confirm current availability, documents and commercial terms for the exact model you select.

Does the supplied catalogue include an OPzV model table?+

No separate OPzV table is identifiable in the supplied pages. The published comparison therefore uses NPFG sealed GEL and OPzS flooded tubular models and requires a separate current OPzV document for an OPzV quotation.

What is the key difference between NPFG and OPzS?+

NPFG is sealed front-terminal GEL in 12V blocks; OPzS is a flooded tubular 2V cell requiring a maintained installation.

What OPzS capacities are listed?+

The catalogue lists 2V models from 150Ah through 1000Ah.

What life statements are shown for OPzS?+

The catalogue states 15 years design life in floating condition and more than 1,000 deep cycles.

Why are dry and filled weights both relevant?+

Flooded OPzS cells add electrolyte weight at installation, which affects handling, rack and floor loading.

Product inquiry

You do not need a finished specification to contact us.

Send the application, voltage, load, runtime, installation space, quantity and destination you know. We will help turn it into a quote-ready request.