Choose block or cell architecture
NPG 12V blocks simplify smaller banks; GMG 2V cells support larger strings and need rack and connector planning.
NPG / GMG · deep-cycle GEL electrolyte
Pure GEL batteries for standby and repeated cyclic duty, spanning 6V/12V NPG blocks and 2V GMG stationary cells.

Product range
NPG Series is catalogue-described with pure GEL electrolyte, heavy-duty grids, deep-discharge recovery, 500 cycles at 80% DOD and a 12-year floating design-life statement. Its 12V range covers 18–250Ah, plus a 6V 225Ah model. GMG uses 2V cells from 150Ah to 1000Ah with a 15-year catalogue design-life statement for larger stationary banks.
Model comparison
These figures come from the manufacturer catalogue. Ask for the current datasheet before final approval or purchase.
| Series / model | Rating | Size L×W×H (mm) | Weight | 3-hour capacity | 10-hour capacity | 100-hour capacity |
|---|---|---|---|---|---|---|
| NPG / NP55-12-G | 12V 55Ah | 229 × 138 × 214 | 19kg | 42Ah | 55Ah | 60Ah |
| NPG / NP100-12-G | 12V 100Ah | 306 × 168 × 214 | 32.5kg | 75Ah | 99Ah | 105Ah |
| NPG / NP200-12-G | 12V 200Ah | 520 × 238 × 223 | 66kg | 155Ah | 200Ah | 220Ah |
| GMG / GM200-2-G | 2V 200Ah | 173 × 111 × 329 | 15kg | 150Ah | 200Ah | 220Ah |
| GMG / GM600-2-G | 2V 600Ah | 301 × 175 × 331 | 43kg | 450Ah | 600Ah | 620Ah |
| GMG / GM1000-2-G | 2V 1000Ah | 475 × 175 × 328 | 69.2kg | 750Ah | 1000Ah | 1020Ah |
How to choose
Send the information you already have. We can narrow the model list and point out what still needs to be checked.
NPG 12V blocks simplify smaller banks; GMG 2V cells support larger strings and need rack and connector planning.
State DOD, cycles per day, partial-state-of-charge periods and recharge time.
The catalogue lists 2.40–2.45V per cell for cycle service and 2.25–2.30V per cell for float service at 25°C.
Typical applications
Tell us about the equipment and duty cycle. We will help check whether this series is a practical fit.
Use daily load, autonomy and recharge energy to size the bank.
Confirm float settings, outage runtime, cabinet temperature and space.
Account for service interval, transport, temperature and time at partial state of charge.
What you can ask for
Commercial terms vary by model, quantity and destination. Include these questions in your inquiry and we will reply with the current available information.
For an accurate quote
Product FAQ
We will confirm current availability, documents and commercial terms for the exact model you select.
The electrolyte and internal construction differ. Selection should be based on duty, charge profile, temperature and exact model data rather than a general claim that one is always better.
NPG is described with up to 12 years and GMG up to 15 years design life. Conditions and exact-model support must be confirmed.
The catalogue describes sealed batteries as operable vertically or horizontally. Installation instructions for the exact model still govern.
The catalogue states −35°C to 45°C for the GEL family.
Lead-acid batteries deliver less Ah at higher discharge rates. Use the rate closest to the actual runtime.
Product inquiry